logo
Home page Contact
Home Contact
Electrical Transducers
LP-1W4S Watt Transducer

LP-1W4S data sheet.

LP-1W4S Single Element Watt Transducer

The LP-1W4S single element watt transducer converts ac current and voltage signals into a dc output signal proportional to the active power flowing in the circuit.

The transducer is designed for 3 phase 4 wire systems with a balanced load.
The output of the transducer is unidirectional only.

Ordering information: LP-1W4S, inputs including CT & VT ratios, output, calibration, power supply.
Example: LP-1W4S, inputs 250/5A 400V, output 4-20mA, 0-200kW, 230Vac supply


Basic Specifications:
InputsAC current and voltage, 3-phase 3 wire balanced load
Current: 0 - 1A or 0 - 5A (others on request)
Voltage: All ac system voltages to 440V
Frequency: 50Hz, 60Hz
OutputLoad independent dc current and voltage
(others on request): 0 - 10mA dc <1500Ω load
: 0 - 20mA dc <750Ω load
: 4 - 20mA dc <750Ω load
: 0 - 5V dc >2kΩ load
: 0 - 10V dc >2kΩ load
Accuracy: Class 0.5 to IEC 60688
Range: 0 to 120% of nominal input
Power Supply: 24V, 110V, 230/240V ac ±20%, 1.5VA
: 24V or 110V dc ±20%, 2W
IsolationGalvanic isolation between inputs, output circuit and auxiliary supply
Test voltage: 4kV 50Hz ac for 1 minute
TemperatureOperating: 0°C to +23°C to +60°C
EMC Approvals: AS/NZS 3548
C-Tick Mark: C-Tick Mark approved
Dimensions
LP-4M
NZ flag
Carrel Electrade Limited
Proudly 100% New Zealand owned and operated.