LP-ID MODBUS® RTU Current Transducer

Data sheet
Modbus Instructions

LP-ID MODBUS® RTU Current Transducer

The LP-ID transducer converts an ac current input into an output signal which is proportional to the rectified arithmetic mean of the input.
Accurate measurement assumes a sinusoidal input waveform.
The output of the transducer is via RS485 serial data bus using MODBUS® RTU protocol.

Ordering information: LP-ID, input, power supply.
Example: LP-ID, input 0-1A, supply 110Vdc.


Basic Specifications:
InputRanges: 1A, 5A (others on request)
Burden: <0.1VA
Overload: 2xInom continuous, 20xInom for 3 seconds
Frequency: 50Hz, 60Hz
OutputRS-485 standard up to 32 stations on a twisted pair cable
Protocol: MODBUS® RTU
Data register: Unsigned 16 bit or signed 15 bit at location 40001
Baud rate: 9600 or 19200
Accuracy: Class 0.5 to IEC 60688
Range: 0 to 120% of nominal input
Power Supply: 24V, 110V, 230/240V ac ±20%, 1.5VA
: 24V dc ±20% or 110V/125V dc (88V-138V), 2W
IsolationGalvanic isolation between input, output circuit and auxiliary supply
Test voltage: 4kV 50Hz ac for 1 minute
TemperatureOperating: 0°C to +23°C to +60°C