Electrical Transducers
|
|
|
Model T-ILC
|
T-ILC Loop Powered Current Transducer
The T-ILC current transducer converts an ac current input into a load independent 4 to 20mA dc signal capable of driving a number of independent instruments.
Accurate measurement assumes a sinusoidal input waveform.
The transducer has a built in ring type current transformer (CT).
The input is achieved by passing the current carrying conductor through the CT.
Standard input current ranges from 0-5A to 0-250A.
Power for the unit is derived from the loop current.
|
| Basic Specifications: |
| Input | Sinusoidal alternating current |
| Standard ranges | : 0-5A, 0-10A, 0-15A, 0-20A, 0-50A, 0-100A, 0-150A, 0-200A, 0-250A |
| Bore sizes | : 12mm & 18mm |
| Frequency | : 50Hz, 60Hz |
| Output | Load independent dc current |
| | : 4 - 20mA dc <750Ω load |
| Accuracy | | : Class 0.5 to IEC 60688 |
| Range | : 0 to 120% of nominal input |
| Loop Supply | | : 10 - 30V dc |
| Isolation | Galvanic isolation between input & output circuits |
| Test voltage | : 4kV 50Hz ac for 1 minute |
| Temperature | Operating | : -10°C to +20°C to +50°C |
| EMC Compliance | : AS/NZS 61000.6.3:2012 |
|
|