|
Electrical Transducers
|
|
|
Model T-ILE
|
T-ILE Loop Powered Current Transducer
The T-ILE current transducer converts an ac current input into a load independent 4 to 20mA dc signal capable of driving a number of independent instruments.
Accurate measurement assumes a sinusoidal input waveform.
The transducer has a built in ring type current transformer (CT).
The input is achieved by passing the current carrying conductor through the CT.
Standard input current ranges from 0-5A to 0-100A.
Power for the unit is derived from the loop current.
|
Basic Specifications: |
Input | Sinusoidal alternating current |
| Ranges | : 5A, 10A, 15A, 25A, 50A, 100A (others on request) |
| Frequency | : 50Hz, 60Hz |
Output | Load independent dc current |
| | : 4 - 20mA dc <750Ω load |
Accuracy | | : Class 0.5 to IEC 60688 |
| Range | : 0 to 120% of nominal input |
Loop Supply | | : 10 - 30V dc |
Isolation | Galvanic isolation between input & output circuits |
| Test voltage | : 4kV 50Hz ac for 1 minute |
Temperature | Operating | : -10°C to +20°C to +50°C |
EMC Compliance | : AS/NZS 61000.6.3:2012 |
Dimensions |
|
|
|