logo
Home page Contact
Home Contact
Electrical Transducers
T-IS Self Powered Current Transducer

T-IS Self Powered Current Transducer

The T-IS current transducer converts an ac current input into a dc output signal which is proportional to the rms calibrated rectified arithmetic mean of the input.
Accurate measurement assumes a sinusoidal input waveform.
Power for the unit is derived from the input signal.


Basic Specifications:
InputsRanges: 1A, 5A (others on request)
Burden: <1.2VA, <2VA for 0-20mA versions
Overload: 2xInom continuous, 20xInom for 3 seconds
Frequency: 50Hz, 60Hz
OutputsLoad independent dc current and voltage
(others on request): 0 - 10mA dc <1500Ω load
: 0 - 20mA dc <750Ω load
: 0 - 5V dc >2kΩ load
: 0 - 10V dc >2kΩ load
Accuracy: Class 0.5 to IEC 60688
Range: 5 to 120% Inom for current outputs
: 20 to 120% Inom for voltage outputs
IsolationGalvanic isolation between input and output circuits
Test voltage: 4kV 50Hz ac for 1 minute
TemperatureOperating: -10°C to +20°C to +50°C
EMC Compliance: AS/NZS 61000.6.3:2012

Dimensions
NZ flag
Carrel Electrade Limited